Resonance Suppression Method for Grid-Connected Converter with LCL filter under Discontinuous PWM

Citations

WEB OF SCIENCE

6
Citations

SCOPUS

7

초록

This paper presents a resonance suppression method that reduces current oscillation incurred by the LCL-filtered grid-connected converter’s discontinuous PWM (DPWM). First, the cause of LCL resonance is analyzed with an aspect of frequency and time domain for DPWM scheme. Then, voltage references are manipulated to decrease the resonance problem. In the proposed method, pole voltage references at the edge of offset voltage are slightly adjusted to reduce the current oscillation. In addition, a perturb and observe (P&O) technique is adopted to search the magnitude of an edge voltage. Through the simulation and experimental tests, the current oscillation is dramatically reduced while keeping the advantages of DPWM scheme. The proposed method can minimize the switching frequency under the grid harmonics regulation. Author

키워드

active dampingDiscontinuous PWM (DPWM)grid-connected converterLCL resonancesearch algorithmFrequency domain analysisMaximum power point trackersPulse width modulationResonanceSwitching frequencyVoltage measurementCurrent oscillationDiscontinuous PWMFrequency and time domainsGrid-connected convertersHarmonics regulationPerturb and observeResonance suppressionsVoltage referenceTime domain analysis
제목
Resonance Suppression Method for Grid-Connected Converter with LCL filter under Discontinuous PWM
저자
Kim, Hyeon-SikSul, Seung-Ki
DOI
10.1109/ACCESS.2021.3110251
발행일
2021-09
유형
Article in Press
저널명
IEEE Access
9
페이지
124519 ~ 124529